Product Details:
Payment & Shipping Terms:
|
Water Basin: | 304SS Steel Plate | Shell: | Alum-zink Galvanized Steel Plate (S.Korea)δ=2 Mm |
---|---|---|---|
Power Supply: | 380V/3P/50HZ | Water Eliminator: | Anti-corrosion PVC |
Spray Pump: | Cast Iron(Schneider) | Flange: | Stainless Steel |
High Light: | bac closed circuit cooling tower,industrial process cooling system |
Industrial Cooling Coil water Cooling Coil Heat exchange Cooling Coils Evapco Cooling tower Coils BAC Cooling coils:
YZFL-330F Specifications
Heat Reject :330 kw |
Gas Filling Rate :35 kg/minute |
Power of fan :1× 4.0 kw |
Blowing rate: 1× 65000 m3/h |
Spray Pump’s Delivery Lift :10 m |
Spray Pump’s Power : 2.2 kw |
Spray Water Flow Rate : 44.7 m3/h |
Drift Loss : 0.01% m3/h |
Operation Work Pressure: 0.10—0.35 Mpa |
Inet/ Outnet: 1*DN 100mm/ 1*DN 100mm |
DN100:Liquid outlet (Please specify adopted screw standards) |
DN100:Air inlet (Please specify adopted screw standards) |
Compensation water pipe: DN 25 mm |
Discharge pipe: DN 50 mm |
Overflow pipe: DN 80 mm |
Shipping Weight: 1860 kg |
Operating Weight:2860kg |
2280mm×2300mm×3720mm (L*W*H) |
WORKING PRINCIPLE
1,Working fluid (water, oil o other liquid) flowing inside of the coils, which is enwrapped by spray water on the outside. The heat of water is transferred by coil and become the saturated vapor when meet the water and air.
2, the heat is exhausted out of the tower by the tower by the top fan; water is collected back to the bottom tank and circulates continuously. The spray water is cooled down via PVC radiation fin in the process of circulation, and flow is the same direction with the fresh wind. The coil mainly takes sensible heat travel style.
3, the most benefit of this style is can avoid scale formation on the outside of the coil. And this will apply especially to dealing with high temperature fluid (e.g. 60°C) or the fluid need big temperature difference (e.g. 60°C to 32°C).
Main Features
1) Whole suit, it will convenient for customers to operate, and easy to transportation & installation..
2) structure is compact, installation area is less, and also more space is saved to enlarge the coils’ unit heat rejection area.
3) Energy efficient and environmental protection.Running in a high automatization and intellectualization,no pollution.
4) apply to the low cooling temperature(Temp.<45℃ or not higher than the location wet bulb temperature too much )or needs a small cooling range projects (△T=5-10℃)
5) Professional and serious attitude, and attention to detail is the pursuit of supremacy consistent high quality standards, production, products and services. This COUNTER FLOW mini cooling towerused for smelting furnace.